OUTPUT

Output Capacity Details ON LINE MODE: Maximum output capacity ratings are reduced for some nominal voltage settings (127/120/115/110V 900 watts, 100V 810 watts). FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion mode (127/120/115/110V 630 watts / 100V 567 watts).
Output Volt Amp Capacity (VA) 1000
Output kVA capacity (kVA) 1
Output Watt Capacity (watts) 900
Output power factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s) Supported 100V; 110V; 115V; 120V; 127V
Nominal Voltage details 120V factory-default nominal voltage
Frequency compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency compatibility details ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds +/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY MODE: Output is regulated to +/-0.05Hz.
Output voltage regulation (line mode) +/- 2%
Output voltage regulation (Economy line mode) +/- 10%
Output voltage regulation (Battery mode) +/- 3%
Built-in UPS output receptacles 6 5-15R outlet(s)
Built-in output receptacles Two switchable single-outlet 5-15R load banks
Output AC waveform (AC mode) Pure Sine wave
Output AC waveform (battery mode) Pure Sine wave

INPUT

Rated input current (at maximum load) 8.6A
Nominal Input Voltage(s) Supported 100V AC; 110V AC; 115V AC; 120V AC; 127V AC
Nominal input voltage description 120V factory default
UPS input connection type 5-15P
Input circuit breaker 15A
UPS Input cord length (ft.) 10
UPS Input cord length (m) 3
Recommended Electrical Service 15A 120V
Input phase Single-Phase

BATTERY

Full load runtime (minutes) 4.8 min. (900w)
Half load runtime (minutes) 14 min. (450w)
Expandable battery runtime Extended runtime supported via optional external battery packs
External battery pack compatibility BP24V15RT2U (limit 1); BP24V28-2U (limit 1); BP24V70-3U (multi-pack compatible); BP24V36-2US (multi-pack compatible)
Expandable runtime description Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software, see manual for details
DC system voltage (VDC) 24
Battery recharge rate (included batteries) Less than 3 hours recharge to 90% (typical, full load discharge)
Replacement battery cartridge (internal UPS battery replacement) RBC24V-LCD
Battery Access Front panel battery access
Battery replacement description Hot-swappable, user replaceable batteries

VOLTAGE REGULATION

Voltage regulation description Online, double-conversion power conditioning maintains 2% output voltage regulation during brownouts and overvoltages
Overvoltage correction Corrects overvoltages to 150V (0-100% load)
Undervoltage correction Corrects undervoltages to 100V at full load (90V at 100V nominal)
Severe undervoltage correction Corrects brownouts to 70V (70% load) & 55V (33% load)

LEDS ALARMS & SWITCHES

LED Indicators 7 front panel LEDs indicate line power availability, AC to DC conversion, battery mode operation, inverter mode, eco mode operation, bypass mode operation and AC output status
Front panel LCD display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, frequency, operating mode, alarm function and a variety of additional options
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
Alarm cancel operation Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Switches 2 switches control off/on power status and alarm-cancel operation; 2 additional scroll-down and scroll-up / select options enable LCD status viewing and configuration options

SURGE / NOISE SUPPRESSION

UPS AC suppression joule rating 570
UPS AC suppression response time Instantaneous
UPS Dataline suppression 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
EMI / RFI AC noise suppression Yes

PHYSICAL

Installation form factors supported with included accessories 4 post 19 inch rackmount
Installation form factors supported with optional accessories 2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
Primary form factor Rackmount
UPS Power module dimensions (hwd, in) 3.5 x 17.5 x 12.5
UPS Power module dimensions (hwd, cm) 8.9 x 44.4 x 31.8
Rack Height 2U
Secondary form factor Tower (requires 2-9USTAND )
UPS Power module weight (lbs) 29
UPS Power module weight (kg) 13.2
UPS Shipping dimensions (height x width x depth / inches) 9.5 x 20 x 24
UPS Shipping dimensions (height x width x depth / cm) 24.1 x 50.8 x 61
Shipping weight (lbs) 41.5
Shipping weight (kg) 18.8
Cooling method Fan
UPS housing material Steel

ENVIRONMENTAL

Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC mode BTU / hr. (full load) 341
AC economy mode BTU / hr. (full load) 230
Battery mode BTU / hr. (full load) 585
AC economy mode efficiency rating (100% load) 93%
Operating Elevation (ft.) 0-3000m / 0-10,000 ft.
Audible Noise 45 dBA at 1m front side

COMMUNICATIONS

Communications interface USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port description Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications
PowerAlert software Included
Communications cable USB and DB9 cabling included
WatchDog compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications

LINE / BATTERY TRANSFER

Transfer time Zero (0 milliseconds) in double-conversion mode; 4 milliseconds economy mode
Low voltage transfer to battery power (setpoint) 100V at full load (90V full load at 100V nominal setting); 70V at 70% load; 55V at 33% load
High voltage transfer to battery power (setpoint) 150

SPECIAL FEATURES

Cold Start (startup in battery mode during a power failure) Cold-start operation supported
High availability UPS features Automatic inverter bypass; Hot swappable batteries
Green & high efficiency features High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation

CERTIFICATIONS

UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category B (EMI); ROHS (Restriction of Hazardous Substances); ENERGY STAR Qualified

WARRANTY

Product Warranty Period (Worldwide) 2-year limited warranty
Connected Equipment Insurance (U.S., Canada & Puerto Rico) $250,000 Ultimate Lifetime Insurance